Standards Actions & Public Review Drafts > Review Comments > Allow COMMUNICATION_FAILURE in Reliability  

Review Comments: Allow COMMUNICATION_FAILURE in Reliability

Document Title

BSR/ASHRAE Addendum j to ANSI/ASHRAE Standard 135-2004, BACnet-A Data Communication Protocol for Building Automation and Control Networks (Third Public Review Draft) 

Title

Allow COMMUNICATION_FAILURE in Reliability 

Comment Number

003 

Comment Type

Substantive 

Commenter Number

0003 

Component Identifier

j-1, 12.X.7, page 4, a.o. 

Component Type

Clause 

Date Submitted

4/29/2008 8:57 AM 

Supportive

No 

Comment Text

[Add COMMUNICATION_FAILURE to j-1, 12.X.7 Reliability, page 4]
[Same addition to other objects where reasonable]

{NO_FAULT_DETECTED, PROCESS_ERROR, CONFIGURATION_ERROR, COMMUNICATION_FAILURE, UNRELIABLE_OTHER}.

Substantiating Statements_0

 

Responses

Responses 

Comment Approval Date

 

Comment Status

Replied To - Resolved 

Affiliation

Siemens BT 

Last Action

 

Last Action Request Further Contact

 

Last Action Type

New Comment 

Response Status

 

Review Period

 

Start Date

 

End Date

 

AuthorSave

 

ModifiedBySave

 

Assigned Responder/SC/WG

 

Committee Response

 

Reply Status

 

Commenter Reply

OK - Resolved 

Late Comment

 

ANSI Comment

 

Committee Title

SSPC135 

Draft Comment

 

Committee Tag

 

Response Sent

 

Substantiating Statements

Since the Access Point is in relation with objects that may reside in other devices, it should have a means to indicate communication faults that prevent it from normal operation.

This may apply to other objects that are introduced with addendum j.
Attachments
Content Type: Review Comment
Created at 4/29/2008 8:57 AM  by bernhard.isler@siemens.com 
Last modified at 6/19/2011 12:07 AM  by oldtownit