Standards Actions & Public Review Drafts > Comment Responses > 0105/001  

Comment Responses: 0105/001

Title

0105/001 

Comment Title

6.3.2.3 

Date Submitted

9/16/2008 7:05 PM 

Review Action

Rejected 

Reply Deadline

10/30/2008 

Commenter Action

 

Response Text

Thank you for reviewing the draft for ASHRAE Standard 189.1 and offering suggestions relating to section 6.3.2.3 (b) of that document.   In your comment you suggest the following: 


"(b) Cooling towers and evaporative coolers shall be equipped with makeup and blowdown meters, conductivity controllers, 40 micron filtration equipment, and overflow alarms.  Cooling towers shall be equipped with efficient drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counterflow towers and 0.005% for cross-flow towers."  


Micro filtration is not necessarily required nor appropriate for all cooling towers.  The Project Committee agrees that this type of information is appropriate for a User’s Manual and recommends that this be addressed in a that document.

Approval Method

PC Meeting 

Approval Date

6/25/2008 

Approval Meeting Location

Salt Lake City 

Request Further Contact

No 

Response Status

Response Approved 

Response Type

Response 

Checkout Date

 

Checkout User

 

Response Date

9/16/2008 